How to do a fire alarm battery calculation

A fire alarm panel's batteries must carry the system in standby for a set time and then run it in alarm for a set time after main power fails. The calculation is simple arithmetic once you have each device's currents from its data sheet.

The method

  1. Add up the standby current of every device and module powered by the panel or power supply, including the panel itself (quantity × standby amps each).
  2. Add up the alarm current the same way, with all notification appliances operating.
  3. Standby capacity (Ah) = total standby current × standby hours.
  4. Alarm capacity (Ah) = total alarm current × alarm minutes ÷ 60.
  5. Required capacity = (standby Ah + alarm Ah) × (1 + safety margin). Pick the next standard battery size up.

Many standard systems use 24 hours of standby and 5 minutes of alarm, often with a 20% margin, but voice and emergency communication systems frequently need longer alarm durations. Always check the edition your authority having jurisdiction adopted and the panel manufacturer's instructions.

Free calculator

Free calculatorRuns in your browser
Results

Worked example

0.350 A standby × 24 h = 8.40 Ah. 2.100 A alarm × 5/60 h = 0.175 Ah. Sum 8.575 Ah × 1.20 = 10.29 Ah, so a 12 Ah battery is the next common size up.

Totaling 40 devices by hand gets tedious. The Fire Alarm Battery Calculator workbook keeps a row per device and suggests the battery size automatically.